Huawei H12-425_V2.0 Practice Test - Questions Answers

List of questions

Question 1

Report Export Collapse

For FusionModule2000, depending on different layout position, batteries can be deployed in the smart module or out of the smart module.

True
True
False
False
Suggested answer: A
asked 18/09/2024
fabio josca
34 questions

Question 2

Report Export Collapse

After all historical alarms of the NetCol5000-A are deleted, the deletion operation is not logged.

True
True
False
False
Suggested answer: B
asked 18/09/2024
Martin Lundgren
39 questions

Question 3

Report Export Collapse

Commissioning NetCol5000-C drainage devices, after lifting the high float for 5 seconds, two water pumps start working, and the drain abnormal alarm is generated.

True
True
False
False
Suggested answer: A
asked 18/09/2024
BRIAN SCULLION
32 questions

Question 4

Report Export Collapse

The UPS can generate large leakage currents. A circuit breaker equipped with a residual current device (RCD) is not recommended. If leakage protection is required, consider the leakage current of the UPS and downstream devices.

True
True
False
False
Suggested answer: A
asked 18/09/2024
Audrey Buan
32 questions

Question 5

Report Export Collapse

As the altitude increases, the air density decreases, and the heat exchange capability of the air in a unit volume decreases. In this case, NetCol8000-E220 works with derating.

True
True
False
False
Suggested answer: A
asked 18/09/2024
Aparecido Primo
41 questions

Question 6

Report Export Collapse

When connecting chilled water pipes for the NetCol8000-C, fill water and preserve pressure 8 hours after the conversion adapter is connected.

True
True
False
False
Suggested answer: B
asked 18/09/2024
Hector Moreno
40 questions

Question 7

Report Export Collapse

The UPS5000-E-200K works in normal mode. If two ECMs are faulty, how does the UPS work?

The UPS has no output.
The UPS has no output.
The UPS transfers to bypass mode.
The UPS transfers to bypass mode.
The LCD is off, but the UPS still works in normal mode.
The LCD is off, but the UPS still works in normal mode.
The UPS switches to battery mode.
The UPS switches to battery mode.
Suggested answer: B
asked 18/09/2024
C/1094 WOLOGUEDE COTONOU – BENIN STEVE
32 questions

Question 8

Report Export Collapse

Refer to the exhibit.

Huawei H12-425_V2.0 image Question 8 32388 09182024192700000000

2N deployment crossing rows
2N deployment crossing rows
2N deployment without crossing rows
2N deployment without crossing rows
N+1 deployment crossing rows
N+1 deployment crossing rows
N+1 deployment without crossing rows
N+1 deployment without crossing rows
Suggested answer: A
asked 18/09/2024
David Fernando del Villar
44 questions

Question 9

Report Export Collapse

When installing a water-cooled module, what is the minimum distance between the module and the wall?

300 mm
300 mm
400 mm
400 mm
500 mm
500 mm
600 mm
600 mm
Suggested answer: D
asked 18/09/2024
Wendie Canez
39 questions

Question 10

Report Export Collapse

On the ECC800-Pro WebUI, which of the following is the first-level menu of the NMS Application?

System Settings
System Settings
Maintenance
Maintenance
Home
Home
Monitoring
Monitoring
Suggested answer: A
asked 18/09/2024
Yuriy Kitsis
35 questions
Total 55 questions